INFRARED ELECTRICAL INSPECTION

RECOMMENDATION

The defective item "TRANSFORMER 0652" should be:

  Repaired immediately. (>89 Degree rise from reference point)
X Repaired as soon as possible. (50 - 89 Degree rise from reference point)
  Repaired at the next scheduled shut-down. (18-49 Degree rise from reference point)
  Repaired as schedule permits. (<18 Degree rise from reference point)



DATE:


5/20/97


ORDER NO:


117884
TIME: 8:52:36 AM TECHNICIAN: Dave Douglas
PLANT: Weldon VOLTAGE: 480 volts
SECTION: Transformer 0652 MANUFACTURER: Sylvania
EQUIPMENT: Transformer Tap TYPE: N/A
ACTUAL LOAD: 8.6 amps PERCENTAGE OF FULL LOAD: N/A
REFERENCE TEMP: (SP#4) 116.0° F AMBIENT TEMP.: 90.0° F
TEMP. SPOT 1: (SP#1) 188.6° F RISE SPOT 1: (SP#1-SP#4) 72.6° F
TEMP. SPOT 2: (SP#2) 122.5° F RISE SPOT 2: (SP#2-SP#4) 6.5° F

REPAIR RECOMMENDATIONS

SUSPECTED PROBLEM: Loose connection at far right tap connection.
SUGGESTED SOLUTION: Check connection, tighten to specifications.
REPAIR ACTIONS:


Date:__________________Name:__________________________________
Notes:_________________________________________________________